Factory energy monitoring
FreeDOCX

Factory energy monitoring

Sample solution for factory energy monitoring: Modbus multifunction meters, data logger, kWh dashboard, overload alerts.

Downloadable files

  • giam-sat-dien-nang-nha-xuong.docx
    Solution description (Word) · 37 KB
    Download

License CC BY 4.0 — free to use, credit “OctaX.vn”. Demo the production version requires a free account to download.

Want to customize it?

The OctaX assistant adjusts dimensions, content and branding on request — estimated ≈ 8 credits.

✦ Customize with AI

Problem

The factory wants to know energy consumption per production line and detect overloads, phase imbalance and peak hours to cut electricity costs.

Architecture

  1. Each branch cabinet gets 1 multifunction meter with an RS-485 port (Modbus RTU) + current transformers.
  2. The meters share one RS-485 line to the data logger (gateway).
  3. The gateway reads every 5–15 seconds and sends data to the server via MQTT or HTTPS.
  4. Dashboard on OctaX: kWh per shift, peak demand, alerts via Telegram/app.

Bill of materials (for 6 branch cabinets)

ItemSL
3-phase multifunction meter, RS-4856
Current transformers sized to the cabinet's rated current18
Gateway Modbus → MQTT/4G1
Shielded twisted-pair cable, 120 Ω termination resistor1 lot

Deployment notes

  • Assign a different Modbus address to each meter; use the same baud rate.
  • Wiring inside the electrical cabinet must be done by a certified electrician; cut the power when installing solid-core current transformers.

Related templates